Ellis Holding Power Logo

VULCAN+™ SINGLE CABLE

Data sheet DS03E

Vulcan+ Single Cable

Vulcan+ Single Cable

Single cable formation

Single cable formation
  • Standard duty cable cleat for single cable formation

  • Cable range of Ø18mm – Ø170mm

  • 316L stainless steel frame with A4-70 stainless steel captive closure fixings

  • Low Smoke and Fume Zero Halogen (LSF0H), Phosphorus Free polymeric liners for increased cable protection

  • Fixing options: one or two M10 fixings (cleat size dependent, as listed in table)

  • ABS and DNV type approved and UL listed

  • Designed, tested and manufactured in accordance with IEC 61914

Part No. Cable Range Dimensions (mm) Weight (g)
Min Ø (mm) Max Ø (mm) W Max D ±1 H ±5 P ±0.5 Fixing Holes (D1)
VRT+00B 18 28 60 54 90 N/A 1 x M10 280
VRT+00A 26 30 60 54 93 N/A 1 x M10 287
VRT+00 30 42 60 54 92 N/A 1 x M10 251
VRT+01 38 50 60 54 100 N/A 1 x M10 258
VRT+02 43 58 68 54 108 N/A 1 x M10 269
VRT+03 49 64 74 54 113 N/A 1 x M10 279
VRT+04 55 70 80 54 119 N/A 1 x M10 284
VRT+05 58 75 85 54 125 N/A 1 x M10 319
VRT+06 63 84 94 54 134 N/A 1 x M10 331
VRT+07 73 90 103 54 140 N/A 1 x M10 391
VRT+08 83 100 110 54 151 N/A 1 x M10 405
VRT+09 86 104 114 54 156 N/A 1 x M10 411
VRT+10 88 110 123 54 162 50 3 x M10 442
VRT+11 90 115 125 54 168 50 3 x M10 453
VRT+12 100 125 135 54 178 50 3 x M10 460
VRT+13 107 132 146 54 185 75 3 x M10 524
VRT+14 120 145 155 54 196 75 3 x M10 536
VRT+15 125 150 160 54 202 75 3 x M10 542
VRT+16 132 153 163 54 206 75 3 x M10 544
VRT+17 136 156 172 54 212 75 3 x M10 618
VRT+18 139 159 172 54 217 75 3 x M10 628
VRT+19 142 162 172 54 222 75 3 x M10 637
VRT+20 160 170 180 54 230 75 3 x M10 646
Ellis Holding Power Logo

VULCAN+™ SINGLE CABLE

Data sheet DS03E

Testing Summary

Vulcan+ Cleats have been tested in line with the International Standard “Cable Cleats for Electrical Installations” IEC 61914. Typical results are detailed below, please note that these testing values are maximums and safety factors appropriate to your application should be used:

Property Classification Clause IEC 61914 Units / Classification Test Data
Cleat type 6.1.3 Composite -
Temp. for permanent application 6.2 °C -40 to +60
UV resistance 6.5.1.2 Xenon arc method A Pass
Corrosion resistance 6.5.2.2 High 316L Stainless steel HAS≥16% Chromium
Impact rating 6.3.4 Very heavy Pass
Flame propagation test 10.0, 10.1 Application time ≥30s Pass
Axial load rating 6.4.3, 9.4 Newtons (N) 110N - Single (VRT+00B = 60N)
Lateral load rating 6.4.2, 9.3 Newtons (N) Horizontal - 200N Vertical - 650N (VRT+00B = 350N)
Resistance to electromechanical force (short circuit testing) 6.4, 6.4.5, 9.5 Cleats at 300mm intervals (withstanding more than one short circuit) single formation 135kA (Report No. PDL-22.079.04) Cable OD= Ø36mm Phase spacing = 125mm
Resistance to electromechanical force (short circuit testing) 6.4, 6.4.5, 9.5 Cleats at 600mm intervals (withstanding more than one short circuit) single formation 149kA (Report No. LCOE 2025 09 3S 0695-3) Cable OD= Ø35.1mm Phase spacing = 125mm

Lateral load: vertical direction

Lateral load: vertical direction

Lateral load: horizontal direction

Lateral load: horizontal direction
DNV

Listed sizes: VRT+00 to VRT+20

ABS Type Approved Product
UL Listed

Conduit & cable hardware 4CG8 with AH-2 & wet locations. Listed sizes: VRT+00 to VRT+18.

London Underground

Vulcan+ Cable Cleats are compliant with the requiremnts of LUL-1085. Product register number 361.