Ellis Holding Power Logo

VULCAN+™ QUAD

Data sheet DS04E

Vulcan+ Quad

Vulcan+ Quad

Quad cable formation

Quad cable formation
  • Standard duty cable cleat for quad cable formation

  • Cable range of Ø10mm – Ø70mm

  • 316L stainless steel frame with A4-70 stainless steel captive closure fixings

  • Low Smoke and Fume Zero Halogen (LSF0H), Phosphorus Free polymeric liners for increased cable protection

  • Fixing options: one or two M10 fixings (cleat size dependent as listed in table)

  • ABS type approved and UL listed

  • Designed, tested and manufactured in accordance with IEC 61914

Part No. Cable Range Dimensions (mm) Weight (g)
Min Ø (mm) Max Ø (mm) W H D P Fixing Holes (D1)
VRQ+00C 10 13 63 93 54 N/A 1 x M10 287
VRQ+00B 13 18 67 97 54 N/A 1 x M10 280
VRQ+00A 18 20 70 106 54 N/A 1 x M10 291
VRQ+00 19 23 74 113 54 N/A 1 x M10 317
VRQ+01 23 25 68 110 54 N/A 1 x M10 284
VRQ+02 26 27 70 113 54 N/A 1 x M10 286
VRQ+03 28 31 78 128 54 N/A 1 x M10 318
VRQ+03A 31 35 90 138 54 N/A 1 x M10 326
VRQ+04 35 42 103 148 54 N/A 1 x M10 378
VRQ+05 43 47 120 165 54 N/A 1 x M10 452
VRQ+06 48 50 121 170 54 N/A 1 x M10 467
VRQ+07 51 57 140 190 54 N/A 1 x M10 523
VRQ+08 58 63 150 200 54 50 3 x M10 541
VRQ+09 64 70 170 218 54 50 3 x M10 581
Ellis Holding Power Logo

VULCAN+™ QUAD

Data sheet DS04E

Testing Summary

Vulcan+ Cleats have been tested in line with the International Standard ‘Cable Cleats for Electrical Installations’ IEC 61914. Typical results are detailed below, please note that these testing values are maximums and safety factors appropriate to your application should be used:

Property Classification Clause IEC 61914 Units / Classification Test Data
Cleat type 6.1.3 Composite -
Temp. for permanent application 6.2 °C -40 to +60
UV resistance 6.5.1.2 Xenon arc method A Pass
Corrosion resistance 6.5.2.2 High 316L stainless steel HAS≥16% chromium
Impact rating 6.3.4 Very heavy Pass
Flame propagation test 10.0, 10.1 Application time ≥30s Pass
Axial load rating 6.4.3, 9.4 Newtons (N) 100N
Lateral load rating 6.4.2, 9.3 Newtons (N) Horizontal - 100N Vertical - 350N
Resistance to electromechanical force (short circuit testing) 6.4, 6.4.5, 9.5 Cleats at 300mm intervals (withstanding more than one short circuit) 134kA (Report No. PDL-22.079.03) Cable OD= Ø36mm
Resistance to electromechanical force (short circuit testing) 6.4, 6.4.5, 9.5 Cleats at 600mm intervals (withstanding more than one short circuit) 119kA (Report No. LCOE 2025 05 35 0317-7) Cable OD= Ø37.5mm

Lateral load: vertical direction

Lateral load: vertical direction

Lateral load: horizontal direction

Lateral load: horizontal direction

Conduit & cable hardware 4CG8 with AH-2 & wet locations. Listed sizes: VRQ+01 to VRQ+09.

London Underground

Vulcan+ Cable Cleats are compliant with the requirements of LUL-1085. Product register number 361.

ABS Type Approved Product
UL Listed

Conduit & cable hardware 4CG8 with AH-2 & wet locations. Listed sizes: VRQ+01 to VRQ+09.

London Underground

Vulcan+ Cable Cleats are compliant with the requiremnts of LUL-1085. Product register number 361.