PROTECT™
Data sheet DS11E
Protect
Trefoil formation
Standard duty intermediate strap for trefoil cables
Utilised between fixed cleats to offer a more cost-effective installation, whilst maintaining short circuit protection
Strap size and dimensional data available on request
316L stainless steel frame with A4-70 stainless steel closure fixing
Low Smoke and Fume Zero Halogen (LSF0H), Phosphorus Free polymeric liner for increased cable protection
Designed, tested and manufactured in accordance with IEC 61914
Consult Ellis for sizing
Testing Summary
Protect has been tested in line with the International Standard ‘Cable Cleats for Electrical Installations’ IEC 61914. Typical results are detailed below, please note that these testing values are maximums and safety factors appropriate to your application should be used:
| Property Classification | Clause IEC 61914 | Units / Classification | Test Data |
|---|---|---|---|
| Cleat type | 6.1.3 | Composite | N/A |
| Temp. for permanent application | 6.2 | °C | -40 to +60 |
| Corrosion resistance | 6.5.2.2 | High | 316L stainless steel has ≥16% chromium |
| Impact rating | 6.3.5 | - | Refer to Ellis |
| Flame propagation test | 10.0, 10.1 | Application time ≥30s | Pass |
| Resistance to electromechanical force (short circuit testing) | 6.4, 6.4.4, 9.5 | Cleats at 300mm intervals (withstanding one short circuit) | 133kA (Report No. PDL-18.071) Cable OD= Ø36mm |