EMPEROR™ SINGLE TWIST FOOT

Data sheet DS40E

Emperor Single Twist Foot

Emperor Single Twist Foot

Single fix twist foot: ES32-39 to ES94-118

Single fix twist foot: ES32-39 to ES94-118

Twin fix twist foot: ES118-130 to ES127-150

Twin fix twist foot: ES118-130 to ES127-150
  • Emperor™ single cable cleat supplied with an integrated twist-foot base fixing kit

  • Designed for rapid installation into 41×41mm and 41×21mm unistrut channel or ladder with inverted rungs

  • All fixings supplied pre-assembled – no additional site fixings required

  • Heavy duty cable cleat for single cable formation

  • Cable range of Ø32mm – Ø150mm

  • 316L stainless steel frame with A4-70 stainless steel captive closure fixings

  • Low smoke and fume zero halogen (LSF0H), phosphorus free polymeric liners for increased cable protection

  • Single-foot versions for cables up to Ø118mm

  • Double-foot versions for cables Ø118mm – Ø150mm

  • Fixing kits available in A4 stainless steel, galvanised steel or zinc-plated steel

  • Designed, tested and manufactured in accordance with IEC 61914

Part No. Cable Range Dimensions (mm) Weight (g)
Min Ø (mm) Max Ø (mm) W H D
ES32-39TFM12-X 32 39 91 92 54 500
ES37-45TFM12-X 37 45 96 96 54 520
ES44-52TFM12-X 44 52 99 101 54 530
ES51-59TFM12-X 51 59 103 105 54 540
ES58-66TFM12-X 58 66 109 104 54 550
ES65-73TFM12-X 65 73 111 106 54 560
ES73-85TFM12-X 73 85 135 115 54 690
ES84-94TFM12-X 84 94 135 138 54 710
ES94-118TFM12-X 94 118 160 153 54 760
ES118-130TTFM10-X 118 130 175 163 70 1000
ES127-150TTFM10-X 127 150 180 183 70 1040

X denotes fixing material, options are as follows: 4 = A4 stainless steel, G = Galvanised steel, Z = Zinc plated steel.

e.g. A ES37-45 with stainless steel twist foot fixings becomes: ES37-45TFM10-4.

Ellis Holding Power Logo

EMPEROR™ SINGLE TWIST FOOT

Data sheet DS40E

Testing Summary

Emperor Cleats have been tested in line with the International Standard “Cable Cleats for Electrical Installations” IEC 61914. Typical results are detailed below, please note that these testing values are maximums and safety factors appropriate to your application should be used:

Property Classification Clause IEC 61914 Units / Classification Test Data
Cleat type 6.1.3 Composite -
Temp. for permanent application 6.2 °C -40 to +60
UV resistance 6.5.1.2 Xenon arc method A Pass
Corrosion resistance 6.5.2.2 High 316L stainless steel has ≥16% chromium
Impact rating 6.3.5 Very heavy Pass
Flame propagation test 10.0, 10.1 Application time ≥30s Pass
Axial load rating 6.4.3, 9.4 Newtons (N) 250N
Lateral load rating 6.4.2, 9.3 Newtons (N) Horizontal - 650N Vertical - 1000N
Resistance to electromechanical force (short circuit testing) 6.4, 6.4.4, 9.5 Cleats at 300mm intervals (withstanding one short circuit) 193kA (Report No. PDL-22.079.05) Cable OD= Ø35mm Phase Spacing = 125mm
Resistance to electromechanical force (short circuit testing) 9.5.2, 9.5.3 Cleats at 600mm intervals (withstanding more than one short circuit) 150kA (Report No. PDL-22.159.1) Cable OD= Ø30mm Phase Spacing = 125mm

Lateral load: vertical direction

Lateral load: vertical direction

Lateral load: horizontal direction

Lateral load: horizontal direction
Click to see how easy the Twist-Foot is to install.
Click to see how easy the Twist-Foot is to install.