Ellis Holding Power Logo

ATLAS™ TREFOIL

Data sheet DS13E

Atlas Trefoil

Atlas Trefoil

Two bolt base fixing

Two bolt base fixing

Single bolt base fixing

Single bolt base fixing

Framing channel base fixing

Framing channel base fixing
  • Standard duty cable cleat for trefoil cable formation

  • Cable range of Ø24mm – Ø102mm

  • Galvanised steel frame with Low Smoke and Fume Zero Halogen (LSF0H), Phosphorus Free polymeric pads to protect the cable sheath

  • Galvanised steel lower fixings and stainless steel top closure fixing to prevent eddy currents

  • Fixing options: single bolt or two bolts

  • Designed, tested and manufactured in accordance with IEC 61914

For full part number please replace XX with the following: TB = Two bolt base fixing, SB = Single bolt base fixing.

Part No. Cable Range Two Bolt Base Fixing Single Bolt Base Fixing Weight (g)
W H D P Fixing Holes (D1) W H D Fixing Holes (D1)
AR2-A31-XX 24-26 170 121 54 150 2 x M10 144 130 54 1 x M10 930
AR2-A32-XX 26-30 170 122 54 150 2 x M10 144 130 54 1 x M10 930
AR2-A33-XX 30-35 170 133 54 150 2 x M10 157 141 54 1 x M10 970
AR2-A34-XX 35-40 170 134 54 150 2 x M10 158 142 54 1 x M10 930
AR3-A35-XX 40-45 198 158 54 175 2 x M10 185 165 54 1 x M10 1200
AR3-A36-XX 45-50 198 160 54 175 2 x M10 187 167 54 1 x M10 1200
AR4-A37-XX 50-55 224 174 54 200 2 x M10 204 182 54 1 x M12 1300
AR4-A38-XX 55-60 224 179 54 200 2 x M10 210 187 54 1 x M12 1300
AR4-A39-XX 60-66 224 185 54 200 2 x M10 217 193 54 1 x M12 1300
AR5-A61-XX 66-71 250 225 54 225 2 x M10 254 225 54 1 x M12 1800
AR5-A62-XX 71-76 250 226 54 225 2 x M10 255 226 54 1 x M12 1800
AR5-A63-XX 76-82 250 230 54 225 2 x M10 260 230 54 1 x M12 1800
AR8-A64-XX 82-92 285 250 54 225 2 x M10 N/A 2100
AR8-A65-XX 92-102 285 250 54 225 2 x M10 N/A 1900
Ellis Holding Power Logo

ATLAS™ TREFOIL

Data sheet DS13E

Testing Summary

Atlas Cleats have been tested in line with the International Standard ‘Cable Cleats for Electrical Installations’ IEC61914. Typical results are detailed below, please note that these testing values are maximums and safety factors appropriate to your application should be used:

Property Classification Clause IEC 61914 Units / Classification Test Data
Cleat type 6.1.3 Composite -
Temp. for permanent application 6.2 °C -40 to +60
Impact rating 6.3.5 Very heavy Pass
Flame propagation test 10.0, 10.1 Application time ≥30s Pass
Axial load rating 6.4.3, 9.4 Newtons (N) Refer to Ellis
Lateral load rating 6.4.2, 9.3 Newtons (N) Refer to Ellis
Resistance to electromechanical force (short circuit testing) 6.4, 6.4.4, 9.5 Cleats at 300mm intervals (withstanding one short circuit) 120kA (Report No. PDL-18.122.7) Cable OD= Ø36mm